The 314.16(B) counting rules
Box fill uses volume allowances. Each allowance takes the per-conductor volume from Table 314.16(B): 18 AWG is 1.50 in³, 16 AWG 1.75, 14 AWG 2.00, 12 AWG 2.25, 10 AWG 2.50, 8 AWG 3.00 and 6 AWG 5.00. Add up the allowances:
- Conductors from outside the box: one allowance each. A wire that passes through unbroken counts once. An unspliced loop at least twice the 300.14 free length counts twice.
- Internal cable clamps: one allowance for all clamps together, based on the largest conductor in the box.
- Support fittings such as luminaire studs and hickeys: one allowance each, based on the largest conductor.
- Device yokes: two allowances per yoke, based on the largest conductor connected to that device.
- Equipment grounding conductors: one allowance for all of them, based on the largest EGC or bonding jumper.
- Pigtails and jumpers that never leave the box, plus small fittings such as locknuts and bushings, do not count.