CFM Calculator

Calculate required airflow in cubic feet per minute from room volume and air changes per hour, or from a heating/cooling load and temperature difference.

Includes the ASHRAE 62.2 whole-house ventilation rate and the 400 CFM per ton rule of thumb.

Last updatedHow we build & check our tools
ft
ft
ft
BTU/h
°F
ft²
Results will appear here once you enter your values.

The two CFM formulas and when to use each

Room volume method: CFM = length × width × height × ACH ÷ 60. Air changes per hour (ACH) is how many times the full volume of the room is replaced each hour; dividing by 60 converts an hourly volume to a per-minute flow. Use it to size an exhaust fan, a supply register for a single room, a garage or workshop fan, or an air purifier target.

Load method (sensible heat equation): CFM = BTU/h ÷ (1.08 × ΔT). The 1.08 constant is 60 minutes per hour × 0.075 lb/ft³ (density of standard air) × 0.24 Btu/lb·°F (specific heat of air). Use it to check how much air a furnace, air handler or duct run must move to deliver a known load at a given supply-air temperature difference. In metric, L/s = W ÷ (1.206 × ΔK), from 1.2 kg/m³ × 1.005 kJ/kg·K.

Worked examples with real numbers

  • Home office: 12 × 12 × 8 ft = 1,152 ft³. At 6 ACH: 1,152 × 6 ÷ 60 = 115.2 CFM (about 54 L/s, 196 m³/h).
  • Furnace airflow: a 40,000 BTU/h sensible load with a 20 °F supply-to-room difference needs 40,000 ÷ (1.08 × 20) = 1,851.9 CFM. The same furnace at a 50 °F temperature rise needs only 741 CFM, which is why heating airflow is much lower than cooling airflow.
  • Cooling rule of thumb: a 3-ton (36,000 BTU/h) air conditioner is typically set for 3 × 400 = 1,200 CFM; in humid climates installers often drop to 350 CFM/ton (1,050 CFM) to improve dehumidification.
  • Whole-house ventilation: a 2,000 ft² home with 3 bedrooms needs 0.03 × 2,000 + 7.5 × (3 + 1) = 60 + 30 = 90 CFM of total continuous ventilation under ASHRAE 62.2-2013 and later (before any infiltration credit).

ASHRAE 62.2 governs whole-house ventilation, not room ACH

Room ACH presets are design rules of thumb for moving air through one space.

Fresh-air ventilation for a dwelling is set by ASHRAE Standard 62.2, which the International Residential Code (IRC M1505) and many energy codes reference.

The formula used here, from the 2013 and later editions, is Q = 0.03 × Afloor + 7.5 × (Nbr + 1).

That is the total ventilation rate; the standard lets you subtract an infiltration credit calculated from a blower-door test, so a leaky house may need a smaller fan.

The older 2010 edition used 0.01 × Afloor, so check which edition your jurisdiction adopted.

Local exhaust also has separate minimums (for example 50 CFM intermittent or 20 CFM continuous for a bathroom, 100 CFM intermittent for a kitchen range hood).

Common mistakes

  • Using total load in the sensible equation. 1.08 × CFM × ΔT covers sensible heat only. Latent load (moisture) is removed at the coil and is not included, so plugging a total cooling capacity in gives an airflow that is too high.
  • Mixing up ΔT. For cooling use room temperature minus supply-air temperature (typically 18–22 °F). For a furnace use the temperature rise printed on the nameplate range (often 35–70 °F).
  • Ignoring altitude. The 0.075 lb/ft³ density is sea-level standard air. At 5,000 ft air is about 17% less dense, so the constant falls to roughly 0.9 and more CFM is needed for the same load.
  • Assuming fan rating equals delivered CFM. Fan ratings are at a stated static pressure; long or undersized ducts (see ACCA Manual D) can cut delivered airflow by a third or more.

Frequently Asked Questions

Common questions about the CFM Calculator

Multiply length × width × ceiling height in feet to get cubic feet, multiply by the air changes per hour you want, then divide by 60. A 12 × 12 × 8 ft room at 6 ACH needs 1,152 × 6 ÷ 60 = 115.2 CFM.

Sources & References

ANSI/ASHRAE Standard 62.2: Ventilation and Acceptable Indoor Air Quality in Residential Buildings

Source of the whole-house mechanical ventilation rate Q = 0.03A + 7.5(Nbr + 1) and local exhaust minimums.

ASHRAE Handbook: Fundamentals (psychrometrics and air properties)

Standard air density (0.075 lb/ft³) and specific heat (0.24 Btu/lb·°F) behind the 1.08 sensible heat constant.

Whole-House Ventilation

DOE guidance on exhaust, supply, balanced and energy-recovery ventilation systems for tight homes.

Manual D: Residential Duct Systems

ANSI-recognized method for sizing duct systems to deliver the design airflow at available static pressure.