How the equal-friction method sizes a duct system
Once you have chosen an air conditioner or furnace, the ductwork has to carry exactly the airflow the blower is built to move. The equal-friction method, the standard way to do this in homes, picks one friction rate and sizes every duct section to lose the same pressure per 100 feet. Each section is then sized from only two numbers: the CFM it carries and the friction rate.
The tool follows these steps:
- System airflow. Cooling: tons x CFM per ton (400 by default). Heating: output BTU/h / (1.08 x temperature rise). The 1.08 is the sensible heat constant for standard air: 60 minutes x 0.075 lb/cu ft x 0.24 BTU/lb-°F.
- Trunk diameter. From the ASHRAE round-duct friction equation, loss = 0.109136 x CFM^1.9 / D^5.02 in. w.g. per 100 ft, solved for D. For 1,200 CFM at 0.08 that gives about 15.6 in, so a 16 in stock duct.
- Branch diameters. Each branch uses the same equation with its own CFM share. 200 CFM at 0.08 needs about 7.9 in, so an 8 in branch.
- Rectangular equivalent. The Huebscher equation converts the round size to a rectangle at the height or aspect ratio you choose.
- Velocity check. Velocity = CFM / duct area, compared with quiet and noisy limits for trunks and branches.
The exponents in the friction equation matter: loss climbs with CFM to the 1.9 power but falls with diameter to the 5.02 power. Going from a 14 in to a 16 in trunk cuts friction by about 49%, which is why a modest bump in duct size is the cheapest way to quiet a system.